Electricity Type: | AC DC | Number Of Main Contacts No: | 3 |
---|---|---|---|
Rated Operational Voltage: | Main Circuit 690 V | Main Circuit Rating: | 16A To 1800A |
Rated Frequency: | Main Circuit 50/60 Hz | Mechanical Durability: | 5 Million |
Highlight: | motor contactor,electrical contactors |
ABB AF260-30 Electrical Contactor Switch AF Types 100-250V AC/DC Contactor 3-phase Motor Contactors
Application
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Operated with wide control voltage range 100-250 V, AC/DC
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
1
Rated Operational Voltage:
Main Circuit 690 V
Rated Frequency (f):
Main Circuit 50/60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 400 A
Rated Operational Current AC-1 (Ie):
(690 V) 55 °C 350 A
(690 V) 40 °C 400 A
(690 V) 70 °C 290 A
Rated Operational Current AC-3 (Ie):
(690 V) 55 °C 220 A
(415 V) 55 °C 260 A
(220 / 230 / 240 V) 55 °C 260 A
(440 V) 55 °C 240 A
(380 / 400 V) 55 °C 260 A
(500 V) 55 °C 240 A
Rated Operational Power AC-3 (Pe):
(220 / 230 / 240 V) 80 kW
(380 / 400 V) 140 kW
(415 V) 140 kW
(440 V) 140 kW
(500 V) 180 kW
(690 V) 200 kW
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 500 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2600 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2400 A
Maximum Electrical Switching Frequency:
AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Mechanical Durability:
5 million
Maximum Mechanical Switching Frequency:
300 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc):
DC Operation 100 ... 250 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 470 V·A
Holding at Max. Rated Control Circuit Voltage DC 2 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 10 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 520 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 470 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 10 V·A
Operate Time:
Between Coil De-energization and NC Contact Closing 25 ... 80 ms
Between Coil De-energization and NO Contact Opening 25 ... 80 ms
Between Coil Energization and NC Contact Opening 30 ... 115 ms
Between Coil Energization and NO Contact Closing 30 ... 115 ms
Connecting Capacity Main Circuit:
Rigid Al-Cable 2 x 95 ... 120 mm²
Bar 32 mm
Rigid Cu-Cable 16 ... 240 mm²
Connecting Capacity Auxiliary Circuit:
Solid 2 x 1 ... 4 mm²
Flexible with Insulated Ferrule 1 x 0.75 ... 2.5 mm²
Stranded 1 x 1 .... 4 mm²
Flexible 2x0.75 ... 2.5 mm²
Flexible with Ferrule 2 x 0.75 ... 2.5 mm²
Product Net Width:
140.0 mm
Product Net Depth / Length:
180.5 mm
Product Net Height:
227.0 mm
Product Net Weight:
6.200 kg
Shipment Terms :
After Service :
We offer guarantee of quality for 180 Days for all the parts we ship out .
1st, we will state the condition of the parts honestly when quote ;
2nd, we will test the quality of the goods before shipment ;
3rd, we will be responsilbe when the parts get in any problems .
Contact Person: Richuang
Tel: +8618158331966