Send Message

Yueqing Richuang Automation Equipment Co.,Ltd

 

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsElectrical Contactor Switch

3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch

3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch

3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch
3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch 3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch 3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch 3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch

Large Image :  3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch Get Best Price

Product Details:
Place of Origin: GERMANY
Certification: CE UL SA
Model Number: 3RT1054-6AP36 3RT1054-6AF36 3RT1054-1AP36
Payment & Shipping Terms:
Minimum Order Quantity: 1 pcs
Price: USD100-200/pcs
Packaging Details: Original Package
Delivery Time: 2-5 work days
Payment Terms: T/T, Western Union, MoneyGram
Supply Ability: 1000pcs/month
Detailed Product Description
Electrical Type: AC/DC Operating Power: 55 KW At 400V
Pole: Three Pole Rated Current: 115A At 400v To 690v
Auxiliary Contacts: 2 NO + 2 NC Operation Voltage: 400 VAC Or 220-240VDC
High Light:

3RT1054-6AP36

,

115A contactor switch

      3RT1054-6AP36 115 A 55 kW MOTOR CONTACTOR 400VAC/ DC 220-240V 2NO 2NC CONTACTOR

 

Power contactor, AC-3 115 A, 55 kW / 400 V AC (50-60 Hz) / DC operation 220-240 V UC Auxiliary contacts 2 NO + 2 NC 3-pole, Size S6 Busbar connections Drive: conventional screw terminal

 
3RT contactors, sizes S00 to S12

Our power range:

  • Contactors for switching motors:
    • Size S00: 3RT201 up to 7.5 kW
    • Size S0: 3RT202 up to 18.5 kW
    • Size S2: 3RT203 up to 37 kW
    • Size S3: 3RT204 up to 55 kW
    • Sizes S6 to S12: 3RT10 up to 250 kW
  • Vacuum contactors for switching motors, see SIRIUS 3RT12 and 3TF6 Vacuum Contactors:
    • Sizes S10 and S12: 3RT12 up to 250 kW
    • Size 14: 3TF6 up to 450 kW

 

Ratings of three-phase motors

The quoted rating (in kW) refers to the output power on the motor shaft (according to the nameplate).

The power rating specifications of the contactors in kW (in accordance with IEC 60947-4-1, Table G) are guide values for 4-pole standard motors at 50 Hz AC and specified voltage (e.g. 400 V AC). The actual starting and rated data of the motor to be switched must be considered when selecting the units. The motor current, motor protection device and the permissible contactor current according to the utilization category must be aligned with each other.

 

Operating mechanism types

3RT1 contactors

The following control and/or operating mechanism versions are available in sizes S6 to S12:

  • Standard operating mechanism with economy circuit for AC and DC operation (switchover from closing coil to holding coil)
  • Solid-state operating mechanism
    Overvoltage damping of the operating mechanism coil is already integrated in the electronics for contactors with solid state operating mechanisms. The operating mechanisms are powered via a supply voltage with an operating range from 0.8 to 1.1 x Us, optionally also controlled depending on the chosen mode of operation. Alternatively, control is also possible via the separate 24 V DC control signal input. Various rated voltage ranges for AC/DC control are available.

    The following versions are available:
    • With two operating modes: Direct control or via CPU input
    • As above, but with additional remaining lifetime indicator (RLT)
    • With fail-safe PLC input for simplification of safety applications (without mode of operation selection)

Technical data

Product brand name SIRIUS
Product designation Power contactor
Product type designation 3RT1
General technical data
Size of contactor S6
Product extension  
● function module for communication No
● Auxiliary switch Yes
Power loss [W] for rated value of the current  
● at AC in hot operating state 21 W
● at AC in hot operating state per pole 7 W
Power loss [W] for rated value of the current without load current share typical 5.2 W
Surge voltage resistance  
● of main circuit rated value 8 kV
● of auxiliary circuit rated value 6 kV
maximum permissible voltage for safe isolation  
● between coil and main contacts acc. to EN 60947-1 690 V
Protection class IP  
● on the front IP00; IP20 on the front with cover / box terminal
● of the terminal IP00
Shock resistance at rectangular impulse  
● at AC 8,5g / 5 ms, 4,2g / 10 ms
● at DC 8,5g / 5 ms, 4,2g / 10 ms
Shock resistance with sine pulse  
● at AC 13,4g / 5 ms, 6,5g / 10 ms
● at DC 13,4g / 5 ms, 6,5g / 10 ms
Mechanical service life (switching cycles)  
● of contactor typical 10 000 000
● of the contactor with added electronics-compatible auxiliary switch block typical 5 000 000
● of the contactor with added auxiliary switch block typical 10 000 000
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level  
● maximum 2 000 m
Ambient temperature  
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C

 

Main circuit
Number of poles for main current circuit 3
Number of NO contacts for main contacts 3
Operating voltage  
● at AC-3 rated value maximum 1 000 V
Operating current  
● at AC-1 at 400 V  
— at ambient temperature 40 °C rated value 160 A
● at AC-1  
— up to 690 V at ambient temperature 40 °C rated value 160 A
— up to 690 V at ambient temperature 60 °C rated value 140 A
— up to 1000 V at ambient temperature 40 °C rated value 80 A
— up to 1000 V at ambient temperature 60 °C rated value 80 A
● at AC-2 at 400 V rated value 115 A
● at AC-3  
— at 400 V rated value 115 A
— at 500 V rated value 115 A
— at 690 V rated value 115 A
— at 1000 V rated value 53 A
● at AC-4 at 400 V rated value 97 A
● at AC-5a up to 690 V rated value 140 A
● at AC-5b up to 400 V rated value 95 A
● at AC-6a  
— up to 230 V for current peak value n=20 rated value 115 A
— up to 400 V for current peak value n=20 rated value 115 A
— up to 500 V for current peak value n=20 rated value 115 A
— up to 690 V for current peak value n=20 rated value 115 A
— up to 1000 V for current peak value n=20 rated value 46.5 A
● at AC-6a  
— up to 230 V for current peak value n=30 rated value 90 A
— up to 400 V for current peak value n=30 rated value 90 A
— up to 500 V for current peak value n=30 rated value 90 A
— up to 690 V for current peak value n=30 rated value 90 A
— up to 1000 V for current peak value n=30 rated value 46.5 A

 

 

Main models: 

3RT1054-1AF36  3RT1054-1AP36  3RT1054-1AV36  3 3RT1054-6AF36 RT1054-6AP36 RT1054-6AV36

3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch 0

3RT1054-6AP36 115 A 55 KW 2no 2nc Contactor Auxiliary Switch 1

Contact Details
Yueqing Richuang Automation Equipment Co.,Ltd

Contact Person: Richuang

Tel: +8618158331966

Send your inquiry directly to us